Cleanroom Testing & Qualification
Coordinate independent cleanroom testing and qualification for a defined room, operating state and contamination-control objective. Laboratory Vortex does not classify, certify or validate facilities itself.
Define the qualification programme
- Document room boundaries, intended ISO particle class, occupancy state (as-built, at-rest or operational), particle sizes and sampling plan.
- Separate commissioning, installation/operational qualification and process-specific performance qualification; agree protocols, acceptance criteria and deviations before testing.
- Include air supply/return layout, pressure cascade, temperature/humidity, equipment and personnel flows and facility change history.
ISO 14644 context and practical tests
ISO 14644-1 concerns classification by airborne particle concentration; ISO 14644-2 concerns monitoring to provide evidence of performance. ISO 14644-3 describes test methods. Verify the edition and applicable scope with the provider. Particle class is not proof of microbiological control or GMP compliance.
- Airborne particle counting and classification: specify particle-size channels, calibrated counters, locations and occupancy conditions.
- Airflow visualization: document smoke/tracer suitability and representative interventions; video alone does not establish aseptic-process validation.
- Installed HEPA filter leakage testing: agree challenge aerosol, scanning method, access and system acceptance criteria.
- Recovery testing: define the challenge, occupancy state and time to a specified particle concentration.
- Viable air/surface/personnel monitoring: risk-based microbiological programme, separate from nonviable particle classification.
Outsource with a usable room brief
- Send room drawings, dimensions, HVAC/filter details, desired classification and relevant manufacturing or research context.
- Specify planned shutdown/access, hazards, cleaning state, test equipment restrictions and whether operations must remain live.
- Agree raw data, calibration traceability, sampling maps, deviations and the report/qualification deliverables; confirm the provider’s actual scope.
Official terminology or method source
Cleanroom Particle, Airflow & HEPA Testing